Skip to product information
1 of 1

Rinnai Commercial Boilers

Rinnai RCB Series Wall-Hung Condensing Boiler, 301 and 399 MBH

Rinnai RCB Series Wall-Hung Condensing Boiler, 301 and 399 MBH

Pricing by quoteAdd this item to your takeoff. A Kingsway Marketing rep will follow up with pricing.
Model

Circulator selection

Per Wilo Boiler Pump Selection Guide, 30°F ΔT, for RCB301AN

Selected pump Select ΔT and pump type
Commonly used accessories

Check the items you need. They are added to this unit’s takeoff line with their Rinnai part numbers. The cascade system sensor goes on its own takeoff line.

Details
Details
Details
Details
Details
Details
  • The above chart should be used as a guide only. Customers may source an equal to the above models but must contact manufacturer(s) directly for recommendation.
  • Each listed Wilo pump selection automatically includes its matching Wilo HV FNPT flange kit on your takeoff.
  • The selected pump and any checked accessories are added to this unit’s takeoff line with their part numbers. The matching Wilo flange kit for the selected pump is added automatically as its own takeoff line right after the unit, same quantity. The cascade system sensor is added as its own takeoff line. Final pump selection is confirmed by your Kingsway rep with the quote.

The Rinnai RCB Series wall-hung boilers (RCB301AN and RCB399AN) are condensing, gas-fired, heat-only hydronic boilers for commercial applications, used as a primary or secondary building heat source. Each has a 316L stainless steel water tube heat exchanger, a 10:1 turndown ratio, and a 7-inch LCD touchscreen control.

RCB301AN: input 30,100 to 301,000 Btu/h; thermal efficiency 97%; AHRI certified heating capacity 254 MBH; heat exchanger surface area 24.6 sq ft; water content 1.8 gal; appliance weight 170 lb; shipping weight 194 lb.
RCB399AN: input 39,900 to 399,000 Btu/h; thermal efficiency 97%; AHRI certified heating capacity 337 MBH; heat exchanger surface area 30.7 sq ft; water content 2.2 gal; appliance weight 183 lb; shipping weight 207 lb.

Dimensions (W x H x D): 19.4 x 35.75 x 21.8 in. Installation: indoor wall-hung. Flue system: Category IV forced draft, direct vent or power vent (room air). Connections: 1 in. NPT gas; 1-1/4 in. NPT supply and return; 4 in. PVC intake and exhaust; 1 in. NPT condensate outlet. Vent materials: PVC, CPVC, PP, and stainless steel. Maximum vent run 140 ft, reduced to 90 ft above 2,000 ft altitude. Common vent up to 4 units on 6 in. PVC or PP. Central heating water pressure 14.5 to 87 PSI; MAWP 160 PSI; 75 PSI pressure relief valve included. Gas supply pressure: natural gas 3.5 to 10.5 in. W.C.; propane 8.0 to 13.5 in. W.C. Electrical: 120 VAC, 60 Hz. Ships for natural gas; field convertible to propane with the optional gas conversion kit.

Controls: built-in pump control (boiler, system, and indirect tank pumps), outdoor reset included, integrated Wi-Fi, 0-10V BMS input, built-in Modbus with optional BACnet and LonWorks adapters, and integrated cascade of up to 8 units using standard thermostat wire. Primary/secondary piping is required.

Included accessories: wall mounting bracket with screws, 75 PSI pressure relief valve, outdoor temperature sensor, and documentation.

Certifications as stated by Rinnai: ANSI Z21.13, CSA 4.9, ASME; ASME "H" stamped and National Board listed. Canada CRN Y6325.2C.

Warranty as stated by Rinnai: heat exchanger 10 years (non-prorated); all other parts and components 1 year; reasonable labor 1 year. See the Rinnai Commercial Boiler Warranty for complete details. Specifications as stated by Rinnai and subject to change by the manufacturer.

Lead time is confirmed when we quote.

Documents: Spec Sheet (Wall-Hung) | RCB Series Brochure

Image is for illustration only. Refer to the product spec sheet for exact dimensions and configuration, and confirm with Kingsway Marketing LLC before you request a quote.

Product selection, sizing and code compliance remain the responsibility of the design professional and the authority having jurisdiction.

View full details