Rinnai Commercial Boilers
Rinnai RCB Series Floor-Standing Condensing Boiler, 500 to 1000 MBH
Rinnai RCB Series Floor-Standing Condensing Boiler, 500 to 1000 MBH
Circulator selection
Per Wilo Boiler Pump Selection Guide, 30°F ΔT, for RCB500AN
- The above chart should be used as a guide only. Customers may source an equal to the above models but must contact manufacturer(s) directly for recommendation.
- Each listed Wilo pump selection automatically includes its matching Wilo HV FNPT flange kit on your takeoff.
- The selected pump and any checked accessories are added to this unit’s takeoff line with their part numbers. The matching Wilo flange kit for the selected pump is added automatically as its own takeoff line right after the unit, same quantity. The cascade system sensor is added as its own takeoff line. Final pump selection is confirmed by your Kingsway rep with the quote.
Couldn't load pickup availability
The Rinnai RCB Series floor-standing boilers (RCB500AN, RCB750AN, and RCB1000AN) are condensing, gas-fired, heat-only hydronic boilers for commercial applications, used as a primary or secondary building heat source. Each has a 316L stainless steel water tube heat exchanger, a 10:1 turndown ratio, and a 7-inch LCD touchscreen control.
RCB500AN: input 50,000 to 500,000 Btu/h; thermal efficiency 97%; dimensions (W x H x D) 21.75 x 39.5 x 30.75 in.; heat exchanger surface area 36.8 sq ft; water content 2.7 gal; gas inlet 1 in. NPT; supply/return 1.5 in. NPT; intake/exhaust 4 in. PVC; appliance weight 243 lb; shipping weight 300 lb.
RCB750AN: input 75,000 to 750,000 Btu/h; thermal efficiency 97.5%; dimensions 28.5 x 44.5 x 51.75 in.; heat exchanger surface area 60.9 sq ft; water content 6.6 gal; gas inlet 1.25 in. NPT; supply/return 2 in. NPT; intake/exhaust 6 in. PVC; appliance weight 525 lb; shipping weight 591 lb.
RCB1000AN: input 99,900 to 999,000 Btu/h; thermal efficiency 98%; dimensions 28.5 x 44.5 x 51.75 in.; heat exchanger surface area 75.4 sq ft; water content 8.1 gal; gas inlet 2 in. NPT; supply/return 2 in. NPT; intake/exhaust 6 in. PVC; appliance weight 567 lb; shipping weight 633 lb.
Installation: indoor floor-standing, direct vent or non-direct vent (room air). Rolls onto the job site on locking casters with leveling feet; at 28.5 in. wide, the largest models fit through a standard commercial doorway. Service panel key on RCB750AN and RCB1000AN. Vent materials: PVC, CPVC, PP, and stainless steel; maximum vent run 140 ft (RCB500AN reduced to 110 ft above 2,000 ft altitude). Common vent up to 2 million Btu/h. Maximum installation altitude 10,200 ft. Central heating minimum water pressure 14.5 PSI; MAWP 160 PSI; 75 PSI pressure relief valve included. Gas supply pressure: natural gas 3.5 to 10.5 in. W.C.; propane 8.0 to 13.5 in. W.C. Electrical: 120 VAC, 60 Hz, 20 A maximum current; integrated 3 pump relays up to 5 A each. Ships for natural gas; field convertible to propane with the optional gas conversion kit.
Controls: built-in pump control (boiler, system, and indirect tank pumps), outdoor reset included, integrated Wi-Fi, 0-10V BMS input, built-in Modbus with optional BACnet and LonWorks adapters, and integrated cascade of up to 8 units using standard thermostat wire. Primary/secondary piping is required. Optional ASME CSD-1 devices: water temperature high limit, high and low gas pressure switches, and low water cut-off.
Included accessories: 75 PSI pressure relief valve, outdoor temperature sensor, temperature and pressure gauge, and documentation.
Certifications as stated by Rinnai: ANSI Z21.13, CSA 4.9, ASME; ASME "H" stamped and National Board listed. Canada CRN Y6325.2C / R5402.5C.
Warranty as stated by Rinnai: heat exchanger 10 years (non-prorated); all other parts and components 1 year; reasonable labor 1 year. See the Rinnai Commercial Boiler Warranty for complete details. Specifications as stated by Rinnai and subject to change by the manufacturer.
Lead time is confirmed when we quote.
Documents: Spec Sheet (Floor-Standing) | RCB Series Brochure
Image is for illustration only. Refer to the product spec sheet for exact dimensions and configuration, and confirm with Kingsway Marketing LLC before you request a quote.
Product selection, sizing and code compliance remain the responsibility of the design professional and the authority having jurisdiction.
Share